Enter the size of the room and what it is made of, then add Sonitus products. The chart shows the reverberation time before and after treatment against the reference range for the way the room is used. Every product is calculated with its own ISO 354 measurement.

Room acoustics calculator

www.sonitus.eu ·

1Room

For an L-shaped or irregular room with a flat ceiling: type the floor area and the total length of all walls. To draw the shape, use the 3D planner.

Floor area · Volume · Surfaces

2The room as it is

Windows, doors, curtains, carpets

Their area is taken off the surface they are on.

Furniture

Your own materials

A material that is not on the list? Enter its sound absorption coefficients from the manufacturer's data sheet.

Measured reverberation time

Enter T20 or T30 per octave band, measured without people. The treatment is then calculated on top of your measurement; the estimate from the materials is drawn as a dashed line for comparison.

3Acoustic treatment

Add the products you want to try. The result on the right updates immediately.

Calculation settings

All three formulas use the same absorption data; they differ in how they treat strongly or unevenly damped rooms.

How it is calculated

Reverberation time. T is calculated for the six octave bands from 125 Hz to 4 kHz from the volume of the room, its surfaces and their sound absorption, with Eyring's formula: T = 0.161 · V / (−S · ln(1 − ᾱ) + 4mV). This is the formula the Croatian regulation on building acoustics (NN 71/2025, annex D) requires once the mean absorption coefficient exceeds 0.2, which is the case in almost every treated room. Sabine's formula (EN 12354-6) and the Arau-Puchades formula for unevenly distributed absorption can be chosen in the settings. Air absorption follows EN 12354-6, or ISO 9613-1 for your own temperature and humidity.

Our products. Each product is calculated with the sound absorption coefficients αs measured in a reverberation room according to ISO 354, for the mounting you choose (directly on the surface or with an air gap). The third-octave values of the test report are averaged into octave bands as in ISO 11654. A panel adds its absorption and takes away that of the surface it covers. The test reports are in the download area.

Reference ranges. For rooms where people speak, teach, make music or do sports, the target is the required reverberation time Tsoll of DIN 18041:2016 (in Croatia HRN DIN 18041:2024), which depends on the volume, with the permitted deviation per octave band. Since April 2025 the Croatian regulation Tehnički propis o akustici u zgradarstvu (NN 71/2025) makes these values binding for new buildings and reconstructions. They apply to the occupied room (80 % occupancy). For rooms where noise has to be kept down (restaurants, canteens, offices, foyers, waiting rooms) the standard asks for a minimum ratio of absorption area to volume A/V; the calculator shows it as the longest reverberation time that still meets it, for the octave bands 250 Hz to 2 kHz. Offices can also be checked against ASR A3.7 and VDI 2569, rooms in Austria against OIB-Richtlinie 5 and ÖNORM B 8115-3:2023, control rooms against EBU Tech 3276 and ITU-R BS.1116, hi-fi listening rooms against IEC 60268-13, home cinemas against CEDIA/CTA-RP22 and music rehearsal rooms against ISO 23591.

Existing surfaces. The absorption of walls, floors, ceilings, windows, curtains and furniture comes from typical values in the technical literature. Real constructions differ, mostly at low frequencies. If you have a measurement of the reverberation time, enter it: the treatment is then calculated on top of what the room really does.

Low frequencies. Below the Schroeder frequency f = 2000 · √(T/V) a room is ruled by single resonances (room modes) and the reverberation time says little. The calculator lists the lowest modes of a rectangular room; the 3D planner shows the response at the listening position for your loudspeaker and subwoofer positions.

The result is an engineering estimate based on statistical room acoustics, typically within 10 to 20 % in rooms of regular shape with evenly distributed absorption. It does not replace a measurement according to ISO 3382 or the design of an acoustic consultant, and it is not proof of compliance with a regulation.